Capacity New Buildings Old Buildings Greenhouses Greenhouses
(kW) with average insulation with average insulation double glassing without insulation
TEMPERATURE DIFFERENCE 30
0
C
5 70-150 m
3
60-110 m
3
35 m
2
18 m
2
10 150-300 m
3
130-220 m
3
70 m
2
37 m
2
20 320-600 m
3
240-440 m
3
140 m
2
74 m
2
30 650-1000 m
3
460-650 m
3
210 m
2
110 m
2
40 1050-1300 m
3
650-890 m
3
300 m
2
150 m
2
50 1350-1600 m
3
900-1100 m
3
370 m
2
180 m
2
60 1650-2000 m
3
1150-1350 m
3
440 m
2
220 m
2
75 2100-2500 m
3
1400-1650 m
3
550 m
2
280 m
2
100 2600-3300 m
3
1700-2200 m
3
740 m
2
370 m
2
125 3400-4100 m
3
2300-2700 m
3
920 m
2
460 m
2
150 4200-5000 m
3
2800-3300 m
3
1100 m
2
550 m
2
200 5000-6500 m
3
3400-4400 m
3
1480 m
2
740 m
2
4
Basic formula
V x T x K = kcal/h
Before choosing your
heater you need to determine
the minimum power required
for your application
Key:
V = Volume of area to be heated
(width x length x height) in m
3
T - Difference between the
external temperature and the
desired internal temperature
(in
0
c)
K - Dispersion coefficient
V = Width 4mt, Length 12mt,
Height 3mt.
Volume of area to be
heated = 144 m
3
Example:
Thermal power required
144 x 23 x4= 13 248 kcal/h
(V x T x K = kcal/h)
1 kW = 860 kcal/h
1 kcal/h = 3.97 Btu/h
1 kW = 3.412 kcal/h
1 kcal/h = 0.252 Btu/h
Now you can choose the heater
which best suits your application.
K = This factor is determined
by the type of construction
and insulation
T = External temperature - 5
0
c
Internal temperature
required +18
0
c
temperature T = 23
0
c
Approximate heating requirements for different building insulation types
Lumens Chart
Formula for calculating heating requirements
Dehumidifiers can be used in a large number of applications but a dehumidifier has to have
appropriate power to fulfil its purpose. Read about ways to select the right dehumidifier and
use the efficiency calculator we developed for you.
Formula for calculating recommended air displacement of dehumidifier:
V x 3 = [m
3
/h]
(Lx W x H) x 3 = m
3
/h
Example: Accommodation:
Width: 4m
High: 4m
Length: 5m
V = 4 x 4 x 5 = 80 m
3
Recommended dehumidifier’s air displacement = 80 x 3 = 240 m
3
The smallest dehumidifier that you can use in that type of a room is DH721 with air displacement
of 240 m
3
/h. Choosing the bigger capacity dehumidifier can shorten the drying process.
Please remember that too quick drying can damage the dying surface,
Dehumidifier selection principle
Air Conditioning Cooling requirements
A STEP BY STEP GUIDE TO THE COOLING REQUIREMENTS
FOR THE AVERAGE OFFICE
Calculate the volume of the area to be cooled in cubic metres,
Width x Height x Depth and multiply this volume x 42. (This gives
the area requirements in Watts). N.B. If this area size is calculated
in cu ft., divide by 35 to give the size in cubic metres.
This chart should be used as a guide only.
A) Number of people .......... x 150watt = ..........
B) Number of computers .......... x 200watt = ..........
C) Number of printers .......... x 250watt = ..........
D) Number of fax machines .......... x 150watt = ...........
E) Tea/Coffee machines .......... x 1000watt = ..........
Total watts ..........
+ Room watts ..........
Grand Total in watts ..........
www.hscuk.co.uk
www.hscuk.co.uk
LIGHTING, HEATING, DRYING & COOLING REQUIREMENTS GUIDE
Product Description
Tungsten Halogen Lamp
Elite LED Light
Elite Globe Light
Elite Contractors 2' Light
Elite Plasterers 2' Light
Elite LED Light
Elite LED Light
Elite LED Light
Elite Compact Fluorescent Lamp
Elite Compact Fluorescent Lamp
Elite Plasterers 5' Light
Magnum Fluorescent Lamp
Elite Task Light
Elite LED Light
Elite Apollo Fluorescent Light 2055
Elite Apollo Fluorescent Light 4055
Powerman LED Light
Powerman LED Light
Powerman LED Light
Lumen values supplied by the manufacturer, please use this chart as a guide only.
Wattage
500
30
57
36
36
35
10
20
36
24
58
72
38
60
110
220
30
20
10
Lumen at 2m
9,000
2700
3900
2200
2200
3100
540
1080
2200
2000
4950
4400
2800
5700
8200
16400
2100
1400
1000
Lamp Life
2,000
30,000
6,000
6,000
6,000
50,000
30,000
30,000
6,000
6,000
6,000
6,000
6,000
50,000
8,000
8,000
30,000
30,000
30,000
Appropriate Model -
2.9Kw = 10,000Btu